YD923F load distributor

2018-08-20 11:47      Click£ºtimes
The YD923F load distributor is a multifunctional load distribution and power control module. The basic function of YD923F load distributor is to cooperate with YD923 series electronic governor to control synchronous parallel operation and/or output power of generator set.
 
 
 
Two. Product characteristics:
 
 
 
The functions of the YD923F load distributor include
 
The average load distribution of generating units.
 
Output power control;
 
Monitoring of adverse and positive work;
 
Automatic realization of buffer and disassembly buffer.
 
Differential compensation control for load mutation.
 
It has a power output and can be used to measure the power of the generator.
 
It has a light-emitting tube column, which shows the power level intuitively.
 
 
 
Three, product specifications
 
1. performance parameters
 
Load distribution accuracy: + 3%
 
Working mode: constant speed mode (or speed regulation mode) load distribution and power control.
 
Inverse power monitoring range: - 2%~ - 20%
 
Inverse power monitoring delay: 0.5s~15s
 
Positive power monitoring range: "Kai": 20% - 100% "Guan": 0 - 80%
 
Positive power monitoring delay: 0.4s~30s
 
All relay contact capacity: class C; 1A, 120V AC; 1A, 24V DC
 
 
 
2. power input
 
Three phase AC voltage: line voltage 100~500V
 
Three line current: 0~5A, power 1.25VA
 
DC power supply voltage: 17~32V, with reverse phase protection and transient suppression function.
 
The negative terminal of all batteries in the unit must be short.
 
 
 
Four. Function description
 
1. three-phase power measurement
 
The power of the YD923F series load divider is the active power part of the generator. The measurement is based on the phase comparison between the output current of the current transformer and the output voltage of the generator, so as to measure the active power of the output current of the current transformer. This measurement method has high accuracy and reliability.
 
 
 
2. three-phase AC voltage input
 
 
 
The three-phase voltage of the generator is measured at L1, L2 and L3 (terminals 1 to 3), and the terminal N must be connected to the zero line of the generator. The AC voltage input circuit is isolated from the 24V battery circuit, and the voltage is more than 5000 volts.